Notice: Specifications of the converging drain pipes should be
applicable to the operating capacity of the units.
(1) Drain branch should be connected to the vertical or horizontal part of the main
drain pipe.
(2) Horizontal pipe should not be connected to the vertical pipe that is on the same
level. It should be connected in the following way:
1) Install 3-way connector of drainage pipe joint, as shown in the left figure.
2) Install drain elbow as shown in the middle figure.
3) Install horizontal pipe as shown in the right figure.
3-way connection of
Drainage pipe joint
DC Inverter U-match Series Cassette Type Unit
T-joint converging drain pipes
Connection of drain elbow
33
Connection of horizontal pipe