GiBiDi SC24 Instructions Pour L'installation page 12

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 18
12
UK
5 - ELECTRICAL CONNECTIONS: TERMINAL BOARDS
Terminal
Position
1
2
3
4
M1
5
6
7
8
9
10
11
M2
12
13
14
15
16
17
M3
18
19
Signal
Description
0 Vac
0 Vac output to the BATTERY CHARGER BOARD.
24 Vac
24 Vac output to the BATTERY CHARGER BOARD.
Positive connection to the BATTERY CHARGER BOARD.
+SK BAT
Negative connection to the BATTERY CHARGER BOARD.
-SK BAT
Flashlight output 24V 10W max (slow flashing during opening, off with gate open,
fast flashing during closing);
LAMP
it can also be connected to the battery charger board.
Warning light output 24V 3W max (slow flashing during opening, on fixed with
SPIA
gate open, fast flashing during closing).
Common INPUTS - OUTPUTS.
COM
Common INPUTS - OUTPUTS.
COM
SAFETY
SAFETY DEVICES / STOP (8K2) input, selectable by DIP SW1_10.
/
See description DIP SW1_10 , Chap.8.
STOP
If not used, make a bridge with terminal n°8, using a 8K2 Ω resistance
START
START (N.A.) input. See DIP SW1_1 and SW1_2, Chap.8
PEDESTRIAN (N.A.) input
The pedestrian manoeuvre is made after the closing of this contact or by the
relay 2 of the plug-in two-channels receivers.
Operation in reply to a PEDESTRIAN command:
• Gate closed
PED
• During the opening → IRRELEVANT
• Gate open
• During the closing
PHOTOCELL input (N.C.).
PHOTO
If not used, jumper with terminal 14.
SAFETY DEVICES (8K2) input.
After the intervention of the safety device, the control unit stops the motion, inverts
SAFETY
it for 1 second and waits for a command.
If not used, make a bridge with terminal n°14, using a 8K2 Ω resistance
Common INPUTS - OUTPUTS.
COM
24V motor output, see fig.4.
MOTOR
24V motor output, see fig.4.
MOTOR
+24 Vdc external accessory power supply (photocells, radio, etc.).
+ ACCES
TEST
Power supply +24Vdc for external safety devices tested, 8W Max .
/
Power supply +24Vdc for external devices submitted to ENERGY SAVING.
ENERGY
See operation DIP SW1_4, Chap.8.
SAVING
Common INPUTS - OUTPUTS.
COM
→ OPENS for 10 seconds (not adjustable)
→ IRRELEVANT if the automatic reclosing is enabled,
otherwise CLOSES
→ OPENS completely.
SC24

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

As05690As05700

Table des Matières