ELECTRIC ANTIFREEZE COIL
BEP
(to be placed on the "External air"
intake duct)
Electric heating coil consisting of armored
elements inserted inside a galvanised she-
et metal duct section with circular flanges
and rubber gasket. The electric coil can
be used in premises with air temperature
between -20° C and +40° C and is equipped
with double safety thermostat: one with au-
tomatic reset and one with manual reset.
The purpose of the pre-heating resistan-
ce is to prevent the heat exchanger from
freezing and is controlled from the control
board with PWM modulating logic in order
to maintain the exaust air temperature over
the freezing value. Protection class IP 43.
18
16
14
12
Duct fitted
10
by the installer
8
6
4
2
0
0
500
heat recovery unit
For
resistance
Identification
Rated power
Power supply voltage
Amperes absorbed by the resistance
Circular Flange Diameter
Minimum air flow rate
18
16
14
12
10
8
6
1000
1500
2000
4
2
0
0
500
Fresh air
ENY–P1
BEP 25/2/M
Code
9022113
kW
2,1
V/Hz/Ph
A
9,1
D
mm
250
m
/h
270
3
18
16
14
12
10
8
6
4
2
0
0
2500
3000
1000
1500
2000
ENY–P2
BEP 25/3/M
9022213
3,0
230V 50Hz 1Ph + Pe
13,0
250
300
153
Pressure drop BEP
BEP40/9
500
1000
1500
2000
Air flow rate (m
/h)
3
BEP35/5
BEP25/2
BEP25/3
2500
3000
AIR
ENY–P3
BEP 35/6/T
9022313
6,0
400V 50Hz 3Ph + Pe
8,7
355
600
English
2500
3000
BEP40/9
BEP35/5
BEP25/2
BEP25/3
ENY–P4
BEP 40/9/T
9022413
9,0
13,0
400
690