Télécharger Imprimer la page

Eaton PowerXL DG1 Notice D'installation page 3

Masquer les pouces Voir aussi pour PowerXL DG1:

Publicité

PowerXL DG1 Option Cards
Wire Sizes
Wire Type
Wire Size
Solid Cu –90°C
12–28 AWG (0.2~2.5 mm
Stranded Cu –90°C
12–30 AWG (0.2~2.5 mm
Control Wiring Requirements
Item
Directive
Product
IEC 61800-2
Safety
UL 508C, IEC / EN 61800-5-1
EMC (at default
Immunity: EN / IEC 61800-3, 2nd environment
settings)
Radiated emissions: EN / IEC 61800-3 (Transient Testing included), 1st
environment
Conducted emissions: EN / IEC 61800-3
Category C1: is possible with external filter connected to drive. Please
consult factory
Category C2: with internal filter maximum of 10m motor cable length
Category C3: with internal filter maximum of 50m motor cable length
I/O Card Input / Output
Board
Allowed
Type
Slots
DXG-EXT-3DI3DO1T
A, B
DXG-EXT-1AI2AO
A, B
DXG-EXT-3RO
A, B
DXG-EXT-THER1
A, B
DXG-EXT-6DI
A, B
DXG-EXT-3DI3DO1T: 3 x DI, 3 x DO, 1 x Thermistor, 24 Vdc / EXT Option Card
Terminal Torque
2
)
4.5 in-lb (0.5 Nm)
2
)
4.5 in-lb (0.5 Nm)
Digital Input
Digital Output
ID
(DI)
(DO)
0x3012
3
3
0x3013
0x3014
3
0x3015
0x3016
6
Analog Input
Analog Output
PT100
(AI) (mA / V)
(AO) (mA / V)
Input
1
2
3
Instruction Leaflet IL040022EN
Effective April 2015
EATON
www.eaton.com
3

Publicité