Connection Heat pump
The diagrams provided are simplified for greater clarity.
The protective devices and other accessories required
by the standards are not illustrated. Standard UTE C15-
100 and good practice must be complied
with.Connected or nearby equipment must not generate
excessive interference (directive 2004/108/CE).
Heat
pump
Thermostat input
of the heat pump
The change-over input of the heat pump is not
controlled by the thermostat.
Starting up
Turn the knob to Shutdown and
press the right-hand button for
5 seconds until C100 x:xx is
displayed (maintenance menu
reserved for the installer).
Press OK.
The screen displays CF01.
R
C
1 2 3
5 sec.
- 24 -
CF01 - Correction of room temperature
measurement
If there is a difference between the temperature noted
(thermometer) and the temperature measured and dis-
played by the unit, the menu acts
on the measurement of the probe
so as to compensate for this diffe-
rence (from -4°C to +4°C in steps
of 0.1°C).
T
Press + or - to make your choice,
OK to confirm it and go to the
next menu.
CF02 - AUTO mode temperature display
option
Press + or - to make your choice,
OK to confirm it and go to the
next menu.
Temperature displayed
Continuous room temperature
display
Continuous display of the set-point
- 25 -