LEGRAND Wattstopper EOSW Série Instructions D'installation page 3

Masquer les pouces Voir aussi pour Wattstopper EOSW Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

In Configuration mode, you can change the Time Delay "T", Operation Mode "O", or perform the load assignment or bind the loads.
Step 1 Enter Configuration Mode
Press and Hold "Configuration" Button "C" for 3 Seconds
• For EOSW-111 Load 1 turns ON. (Load 1 is now active.)
• For EOSW-112 Load 1 turns ON and Load 2 turns OFF.(Load 1 is now active.)
• "Time Delay" and "Operating Mode" LED's are lit to indicate their current settings
for the specific load.
Step 2 Modifying "Time Delay"
Tap the "Time Delay" Button "T" to cycle through options of 30min/15min/5min
descending. The corresponding Time Delay LED is lit to confirm time delay selection
for the specific load.
Step 3 Modifying "Operating Mode"
Tap the "Operating Mode" Button "O" to alternate between "Manual-On" and
"Automatic-On" settings where corresponding LED confirms operating mode selection
for the specific load.
Step 4 Modfying Load 2 Parameters (EOSW-112)
To modify Load 2 settings:
Tap "Configuration" Button "C" once to alternate between Loads
• Load 2 turns ON and Load 1 turns OFF. (Load 2 is now active.)
• The load status LED that is lit corresponds to the Load being modified.
• Repeat steps 2 and 3.
Step 5 Exit "Configuration" Mode
Press and hold the "Configuration" Button "C"on the receiver until the green LED's turn
off, approximately 3 seconds, to exit Configuration mode.
SETTING LOAD PARAMETERS ON THE RECEIVER
3
EOSW-112
"Load 1 Status"
Blue LED ON
"Load 2 Status"
Blue LED Off
Configuration
Button
EOSW-112
Time
Delay
LEDs
Time Delay
Button
EOSW-112
Operating
Mode Button
EOSW-112
"Load 1 Status"
Blue LED OFF
"Load 2 Status"
Blue LED ON
Configuration
Button
"Load Status"
Blue LEDS
"Load Status"
Blue LEDS

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Wattstopper eosw-111Wattstopper eosw-112

Table des Matières