Determining The Location Of The Inside And Outside Unit - Qlima SC42 Série Manuel D'installation

Masquer les pouces Voir aussi pour SC42 Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 46
4.

DETERMINING THE LOCATION OF THE INSIDE AND OUTSIDE UNIT.

4.1
Determining the location of the inside unit.
Do not expose the indoor unit to heat or steam.
Select a place where there are no obstacles in front or around the unit.
Make sure that condensation drainage can be conveniently routed away continuously going down-
wards.
Do not install near a doorway.
Ensure that the space on the left and right of the unit is more than 12cm.
Use a wire detector to detect wires and/or electric cables. to locate studs to prevent unnecessary
damage to the wall.
The top of the indoor unit should be installed on the wall at a height of 2.3 metres or more from the
floor.
The indoor unit should be installed allowing a minimum clearance of 15cm from the ceiling.
Be sure to level the indoor unit.
When determining the location of the interior unit take the possible locations of the exterior unit
into account. Interior and exterior part must be linked by piping and cables.
More than 12 cm.
4.2
Determining the location of the exterior unit.
Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
G
NOTE
The outdoor unit produces sound when in use, this could interfere with local legislation. It
is the responsibility of the user to check and to make sure the equipment is in full compliance
with local legislation.
Determine the air outlet direction where the drainaged air is not blocked.
Take the air conditioner weight into account.
If an awning is built over the outdoor unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
Ensure that the clearance around the back of the unit is more than 30 cm and left side is more than 30
cm. The front of the unit should have more than 200 cm of clearance and the connection side (right
side) should have more than 60 cm of clearance. See picture 5.
Be sure to level the outdoor unit
4
74
74
More than 15 cm.
2.3 m or more
More than 12 cm.
Figure 4

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sc52 sérieScja 19 série

Table des Matières