Connection To The Chimney - Nordica ROSSELLA R1 BII Instructions Pour L'installation, L'utilisation Et L'entretien

Masquer les pouces Voir aussi pour ROSSELLA R1 BII:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ROSSELLA R1 BII – LUNA BII
2 m
1
m
CHIMNEY CAPS - DISTANCES AND POSITIONING UNI 10683/98
Inclination of the
roof
α α α α
15°
30°
45°
60°

6. CONNECTION TO THE CHIMNEY

For safety reasons the door of the appliances with constructive system 1, must be opened only for the loading of the
fuel or for removing the ashes, while during the operation and the rest, the door of the hearth must remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open door is
allowed under supervision.
1191015 – EN
10 m
(1) The chimney cap must not show hindrances within 10 m from
walls, pitches and trees. Otherwise raise it of at least 1 m over the
hindrance.
The chimney cap must exceed the ridge of the roof of at least 1 m.
>A
H min.
(1)Ridge axis
α
Distance between the roof
ridge and the stack
A (m)
< 1.85 m
> 1.85 m
< 1.50 m
> 1.50 m
< 1.30 m
> 1.30 m
< 1.20 m
> 1.20 m
> _ A
0,5 m
(2)Roof
Minimum height of the stack
(measured from the outlet)
0.50 m above the roof ridge
1.00 m from the roof
0.50 m above the roof ridge
1.30 m from the roof
0.50 m above the roof ridge
2.00 m from the roof
0.50 m above the roof ridge
2.60 m from the roof
H (m)
Picture 6
Picture 7
21