Reduction of the air intake pipe section and gas output section is strictly forbidden.
Ignore section 4.22 in case of airtight installation.
It must be installed in a room with positive atmospheric pressure (minimum 5 pascals). Never make it
work in depression (airtight rooms or without the due air renovations).
Please note below two kinds of airtight installations:
4.29. "DIFLUX" piping.
The gas outlet and the combustion air inlet are connected to the concentric "Diflux" tube. After the air intake
you will find immediately on the outside, the rest of pipe sections should be in double wall pipe.
q
Air intake pipe.
w
Combustion air intake.
Gas output >2m. Double wall pipe in the
e
outside.
r
Windbreak.
t
Connection of stove to combustion gas outlet.
y
Stainless steel hose clamp.
For these installations it is highly advised to modify the depression offset, according to the number of pipe
sections installed. See the following chart:
Gas
outlet pipe sections
≤ 3m
4m
> 4m
* Check modification over the offset with the stove working on level 1 and 9 during 1 hour, controllong the right
combustión of the stove ( no smoke, no depressure excess, etc).
4.30. Air inlet connected directly to the outside.
EXAMPLES OF AIRTIGHT INSTALLATION.
Offset adjustment
"Depression" (PA)*
+ 5.0
+ 8.0
+8.0 ≥ Adjustment ≤ +14.0
38
r
y
e
w
t
q
w
Drawing 11
Drawing 12