The following measurements must be respected:
Š LOWER PART COLD AIR INLET WITH TOTAL MINIMUM SURFACE 550 CM².
Š UPPER PART HOT AIR OUTLET WITH TOTAL MINIMUM SURFACE 550 CM².
THIS VENTILATION SYSTEM IS TOTALLY INDEPENDENT FROM THE AIR INTAKE FOR COMBUSTION!!
IMPORTANT: ALL OPENINGS MADE FOR PROPER AIR RECIRCULATION MUST BE MADE INACCESSIBLE BY MEANS OF
APPROPRIATE PROTECTIVE GRILLES OR MESHES, ENSURING THE MINIMUM PASSAGE OF AIR REQUIRED.
Minimum 5 cm
THE INSERT MUST LIE AT LEAST 1 CM ABOVE THE FIRE SURFACE IN COVERING MARBLE.
THE FLUE OUTLET PIPE MUST ALWAYS MAINTAIN A MINIMUM DISTANCE OF 50 MM FROM INFLAMMABLE PARTS.
A
B
C
ENGLISH
5 cm
For correct functioning of the insert, during construction of the ue
the measurements between the insert and internal walls of the ue
must be respected ( gure below).
From the clearance measurements of the stove given in the technical
features, it is necessary to consider at least 50 mm of air in the upper
part and on the 2 sides.
It is just as important to guarantee the minimum distance of 5 cm
on both sides as shown in the gures above.
Reference A
Š Hot convection air The heat accumulated inside the
covering must be vented to prevent excessive overheating of
the insert.
Reference B
Š Forced ventilation
The tangential fan distributes the heat developed by the insert
into the environment.
Reference C
Š Air inlet from the room:
To allow air recirculation an air inlet point must be envisioned,
which is preferably positioned in the lower part of the structure in
order to encourage convection. The air must be withdrawn from
the machine's working environment.
5 cm
5 cm
45