Emergency System; Maintenance And Cleaning - Eurofred FAH003Z001 Mode D'emploi Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

If the terminal/control connection does not operate correctly at switch on, the terminal display will read
"88,8" and the LEDs will all be switched off.
9

EMERGENCY SYSTEM

.
PLEASE NOTE: A specialist technical engineer must only perform the operations described here
below.
If the electronic control unit breaks down or presents operating anomalies and it is impossible to
replace it immediately, there is an EMERGENCY SYSTEM that can be used to maintain the unit in
operation until it can be replaced.
To use this system, proceed as follows:
1. Cut off power to the Blocksystem
2. Remove all jumpers between the L terminals and the common contacts of the card relays
(terminals 25-28-33-36-38)
3. As shown in the diagram, connect a thermostat between the L terminal, the NO terminals
(terminals 32,37) and the NC terminal (terminal 34) of the compressor, defrosting and fan
relays (COMP, DEF and FAN)
4. Fit a jumper between the L terminal and the NO terminal of the ON/OFF relay (terminal 26
supplying power to the crankcase heaters, door and waste, where fitted).
5. Connect the Blocksystem back to the mains power, setting the thermostat to the required
temperature.
6. PLEASE NOTE: This connection can only be used momentarily. Contact your dealer as soon as
possible to replace the malfunctioning card.
7. PLEASE NOTE: Defrosting will be cut out for the entire emergency phase and for this reason, we
recommend that cold room door opening be kept to a minimum.
8. When fitting the new control unit, restore all of the connections described in points 2,3,4 and 5.
Key:
T = Thermostat
10.

MAINTENANCE AND CLEANING

• IMPORTANT NOTE: All cleaning and maintenance operations must only be performed when the
Blocksystem is switched off and disconnected from the power supply (thermomagnetic switch set
to off).
• In the event that machine parts need replacing, they have to be replaced by items exactly the
same to the originals ones
• Every week: ensure that the evaporator is clean and that there is no build-up of ice. If the
evaporator is clogged with ice, carry out a manual defrost cycle by holding down the "UP" key for
more than 10 seconds. Repeat this procedure until the evaporator is completely clean. Check
T
BLOCKSYSTEM FA/EA Pag. 57
UK
REV. 02 11/07

Publicité

Table des Matières
loading

Table des Matières