Télécharger Imprimer la page

Brief Overview Of The Pictures On The Display - Siemens PolyCool Superheat CPS 40 Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour PolyCool Superheat CPS 40:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Picture Display
1
Display segment test for about 5 s
2
Selection of the circuit
After selecting the circuit, select the following mode with +/- and press <OK> to confirm.
3
CONF MODE (configuration mode)
4
REFRIG (selection of refrigerant)
5
ENABLE (Enabling/disabling the compressor
and EIV feedback signal)
6
CAP
7
SENSOR
8
RANGE (Measurement range of X4)
9
UNITS
Continously press <ESC> and back to picture 3
10
PARA MODE (parameter mode)
11
T
T SP
(setpoint of superheat)
(6.0 K / 10.8 °F default)
T XP
(P-band superheat)
(10 K / 18 °F default)
T TN
(integral action time superheat)
(30 s default)
T D
(D-part of superheat)
(0 default)
Continously press <ESC> and back to picture 10
12
CAP
CAP SMX (max. setpoint increase)
(18.0 K / 32.4 °F default)
CAP SD
(external signal direction)
(SD=1 indicates that 0 V / 4 mA corresponds
to min. cooling capacity)
CAP SP
(setpoint of capacity control)
(6.0 °C / 42.8 °F default)
CAP XP
(P-band)
(35 K / 63 °F default)
CAP TN
(integral action time)
(5 s default)
Continously press <ESC> and back to picture 12
52/136
Siemens
Building Technologies
8
Brief overview of the pictures
on the display
For the values of the setting variables and their increments, refer
to chapter 5.
CPS40
Procedure
Simutaneously press down +/- buttons
for at least 5 seconds.
Set with +/- and press <OK> to confirm.
Press <OK> to confirm and proceed
In picture 3, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
Press <OK> to confirm and proceed
Press <OK> to confirm and proceed
In picture 11, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
Press <OK> to confirm and proceed
In picture 12, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
CE1U3372XX / H 74 319 0555 0 d
2013-10-01

Publicité

loading