More than 30cm
Fence or barrier
Figure 5
When determining the location of the exterior unit take into account the possible location of the
interior unit. The interior and exterior units must be connected by pipes and cables.
G
TAKE CARE
For the SC42xx & SC52xx models: The length of the piping is 4 metres.
For the S42xx & S52xx(B) & SJA2519 models: For units with a capacity of up to 6.0 kW, the
Do not place animals and plants or other obstacles in the path of the air inlet or outlet.
Always install the air conditioner at an easily accessible location.
Consult and follow local legislation regarding mounting and installation of air conditioner equip-
ment.
In the case that the installation place is exposed to strong wind such as a seaside, make sure the fan
is operating properly by putting the unit lengthwise along the wall or using a dust or shield plates.
See picture 6.
Incorrect
Incorrect
Strong
Strong
wind
wind
Figure 6
If the exterior unit is installed on a roofing structure or exterior wall then it can result in bothersome
noise and vibrations.
Ensure that the exterior unit can be attached to a stable substructure.
4
70
70
More than 30cm
More than 60cm
More than 200cm
maximum pipe length between the inside and the
outside part is 20 metres. For units with a capacity
> 6.0 kW, the maximum pipe length between the
inside and the outside part is 30 metres.
For units with a capacity of up to 6.0 kW, the
maximum difference in height between the inside
and the outside part is 8 metres. For units with a
capacity > 6.0 kW, the maximum difference in height
between the inside and the outside part is 20 metres.
Wall
Barrier
Strong
Strong
wind
wind
More than 60cm
Correct
Correct