TECHNICAL DATA

MODEL
TYPE
OUTPUT
(1)
DELIVERY
(1)
light oil
natural gas
FUEL
Gas pressure at maximum delivery
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
PUMP
delivery (at 12 bar)
pressure range
fuel temperatur
CONFORMITY TO DIRECTIVES
NOISE LEVELS
Sound pressure
(3)
Sound power
APPROVAL
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 4)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
The sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accu-
racy, as set out in EN ISO 3746.
2nd stage
kW
(min - max)
kg/h
kW
1st stage (min)
kg/h
2nd stage
kW
(min - max)
1st stage (min)
kW
Gas: G20/G25
mbar
(2)
number
°C
°C max
kg/h
bar
° C max
dBA
CE
Flame stability disk with circular
sectors 3)(D)p. 16
965 - 1846
81 - 155
488
41
940 - 1730
300
Light oil, viscosity at 20 °C: 6 mm
Natural gas: G20 (methane) - G21 - G22 - G23 - G25
- Intermittent (min. 1 stop in 24 hours)
- Light oil: Two-stage (high and low flame) and single-stage (all - nothing)
- Gas: Progressive two-stage or modulating by kit (see ACCESSOIRES)
Boilers: water, steam, diathermic oil
2009/142/CE - 2006/42/CE - 2014/35/UE - 2014/30/UE
7
RLS 160/M MX
781 T
Flame stability disk without circular
sectors 3)(D)p. 16
1132 - 2013
95 - 169
560
47
940 - 1840
300
2
/s max (1,5 °E - 6 cSt)
14 / 21
2
0 - 40
60
230
10 - 21
90
80.5
91.5
0085BN0625