TECHNICAL DATA

TYPE
Output
Thermal power
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC Directives: 2014/30/UE - 2014/35/UE - 2006/42/CE.
The burner meets protection level of IP 40, EN 60529.
8
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air damper
7 – Hydraulic jack with air damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
2664
23.8 – 35.5 kW
(H
Gas oil, viscosity 4 –6 mm
Single phase, 230 V ± 10%
Run current 0.7 A – 2850 rpm – 298 rad/s
Secondary 8 kV – 16 mA
Pressure: 8 – 15 bar
Fig. 1
7
6
6
9
D6252
HYDRAULIC JACK OPERATION 7)(Fig. 1)
It is strongly recommended a periodic check of
the pump pressure operation (annually or better
every six months, if the burner operation is con-
DANGER
tinuous).
If the value is lower than 1 bar, compared to that
one of the initial setting, please check the clean-
ing of the pump and line filters.
In case the pressure setting was not restorable,
please replace the pump, in order to guarantee
that the pump pressure during the pre-purge time
is at least 3.7 bar.
1
GB
510 T3
2 – 3 kg/h
= 11.86 kWh/kg)