ELECTRICAL WIRING

D4685
Main switch
230V ~ 50Hz
A
3367
TESTING
Check the burner has stopped by opening
the thermostats.
Check the burner's lockout during opera-
tion by interrupting the flame detector.
CONTROL BOX (see fig.11)
To remove the control box from the burner it is necessary to:
Fig. 11
disconnect all the connectors, the 7-pin plug, the high voltage cables and
the earth wire (TB);
unscrew the bolt (A) and pull the control box in the direction of the arrow.
To install the control box it is necessary to:
screw the bolt (A) in at a torque of 1 - 1.2 Nm;
reconnect all the connectors previously disconnected.
NOTE: The burners have been type-approved for intermittent operation.
This means they must stop at least once every 24 hours in order to allow the
electrical control box to check its efficiency on start-up. The boiler limit ther-
mostat (TL) normally ensures the burner halts. If this does not happen a time
switch halting the burner at least once every 24 hours must be applied in se-
ries to limit thermostat (TL).
E9275
WARNING:
Do not swap neutral and phase
over, follow the diagram shown
carefully and carry out a good
earth connection.
The cross section of the wires
must be at least 1 sq. mm. (Un-
less requested otherwise by local
standards and legislation).
The electrical wiring carried out
by the installer must comply with
the rules in force in the country.
(See "Hydraulic systems" on
*
page 5). If any of the hydraulic sys-
tems feature the automatic shutoff
device (230V - max. 0.5A), it must
be connected to terminals N - T2 in
the 7-pin plug.
TO BE DONE BY
THE INSTALLER
6
GB
KEY TO LAYOUT:
B5 – 2 nd stage working si-
gnal
~
(230V
- 0.1A max.)
C
– Capacitor
E
– Electrode
F
– Flame detector
h.. – Hours counter
~
(230V
- 0.1A max.)
MV – Motor
P
– Bridge socket
RS – Remote reset
S3 – Remote lockout signal
~
(230V
- 0.5A max.)
SER – Safety lockout device
T6A – Fuse
TB – Burner earth
TL – Limit thermostat
TR – Adjustment thermostat
TS – Safety thermostat
st
V1 – Oil valve 1
stage
nd
V2 – Oil valve 2
stage
X.. – Plug
XP.. – Socket