2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric
laws/regulations and execute the following instructions by professional personnel.
1)
Make sure the mains wire and breakers in the building are in compliance with the
standard of rated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source 16A for the UPS, as its
rated current is less than the UPS's maximum input current. Otherwise the receptacle may
be burned and destroyed.
2)
Switch off the mains switch in the building before installation.
3)
Turn off all the devices that need to be connected before connecting them to the UPS.
4)
Prepare wires based on the following table:
Model
E3 Pro 5-6k RT
E3 Pro 10k RT
NOTE 1: It is recommended to use suitable wire in above table or thicker for safety and
efficiency. Use imperativelly flexible cables
NOTE 2: The selections for color of wires should be followed by the local electrical laws
and regulations.
5)
Remove the terminal block cover from the rear panel of the UPS. Then connect the
wires according to the following terminal block diagrams: (Connect the ground wire first
when connecting the wires. Disconnect the ground wire last when disconnecting wires!)
Output Line
Output Neutral
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
10
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 01 16 AA 59 204 09
Wiring spec mm² mm²/AWG
Input
Output
6/10
10/8
Terminal Block wiring diagram
Battery
6/12
10/8
Ground
6/12
10/8
Input Neutral
Input Line
Ground