5) Fan Level (Air conditioner, ERV, ERV DX)
Input
Output
Valid Range
NV
SNVT_switch
6) Fan Direction Auto(Air Conditioner), Heater(ERV, ERV DX)
Input
Output
Valid Range
NV
SNVT_switch
Function
Fan Level input
Using NV
network variable : SNVT_switch, nviFanSpeedCmd
Operation
Fan Level control
Function
Fan Level display
Using NV
network variable : SNVT_switch, nvoFanSpeed
Operation
Fan Level monitor
Field
value
state
Fan Direction Auto(Air conditioner), Heater(ERV, ERV DX)
Function
input
Using NV
network variable : SNVT_switch, nviSwing_Heater
Fan Direction Auto(Air conditioner), Heater(ERV, ERV DX)
Operation
control
Fan Direction Auto(Air conditioner), Heater(ERV, ERV DX)
Function
display
Using NV
network variable : SNVT_switch, nvoSwing_Heater
Fan Direction Auto(Air conditioner), Heater(ERV, ERV DX)
Operation
monitor
Field
value
state
Operation
0 = Auto
1 = Low
2 = Medium
3 = High
4 = SuperHig
not used (set in 0 % usually)
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON