LG LonWorks Manuel D'installation page 110

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

100
REMARQUES
4) Chilled Water Outlet Temperature (Turbo Chiller)
Input
Output
Valid Range
5) Hot water(Coolant) Outlet Temperature (Turbo Chiller)
Input
Output
Valid Range
6) Motor Current Limit (Turbo Chiller)
Input
Output
Valid Range
Function
Using NV
Operation
Function
Using NV
Operation
NV
SNVT_temp_p
Function
Using NV
Operation
Function
Using NV
Operation
NV
SNVT_temp_p
Function
Using NV
Operation
Function
Using NV
Operation
NV
SNVT_lev_percent
Cold Water Outlet Temperature input
network variable : SNVT_temp_p, nviCWTemp
Cold Water Outlet Temperature control
Cold Water Outlet Temperature display
network variable : SNVT_temp_p, nvoCWTemp
Cold Water Outlet Temperature monitor
Operation
3 ~ 50 ºC
Hot water(Coolant) Outlet Temperature input
network variable : SNVT_temp_p, nviHWTemp
Hot water(Coolant) Outlet Temperature control
Hot water(Coolant) Outlet Temperature display
network variable : SNVT_temp_p, nvoHWTemp
Hot water(Coolant) Outlet Temperature monitor
Operation
10 ~ 90 ºC
Motor Current Limit input
network variable : SNVT_lev_percent, nviMotorCurLimit
Motor Current Limit control
Motor Current Limit display
network variable : SNVT_lev_percent, nvoMotorCurLimit
Motor Current Limit monitor
Operation
1~100 %