■ Chiller input/output
1) On/Off (Turbo Chiller)
Input
Output
Valid Range
NV
SNVT_switch
2) Alarm release (Turbo Chiller)
Input
Valid Range
NV
SNVT_switch
3) Mode (Turbo Chiller)
Input
Output
Valid Range
NV
SNVT_hvac_mode
Function
On/Off input
Using NV
network variable : SNVT_switch, nviOnOff
Operation
On/Off control
Function
On/Off display
Using NV
network variable : SNVT_switch, nvoOnOff
Operation
On/Off monitor
Field
value
state
Function
Alarm release input
Using NV
network variable : SNVT_switch, nviAlarmRelease
Operation
Alarm release control
Field
value
state
Function
Mode input
Using NV
network variable : SNVT_hvac_mode, nviHeatCool
Operation
Mode control
Function
Mode display
Using NV
network variable : SNVT_hvac_mode, nvoHeatCool
Operation
Mode monitor
Field
value
state
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON
Operation
not used (set in 0 % usually)
HVAC_COOL = COOL
HVAC_HEAT = HEAT