The following settings apply to the 3-point PID controller:
ClO
-controller
2
parameters page 1
(3-point PID)
The set point (W) function is used to specify the nominal value within the measuring range.
Measuring range
0..2 mg/l
The proportionality factors for the P-proportion of the respective controller can be specified
with the proportional area (XP1) and proportional area (XP2) functions.
Value range: 0 % to 999 %
The ID-proportion of the controller can be adjusted with the prelim time (Tv) and delay time
(Tn) functions.
Value range:
Switching point 2 can be adjusted with the set point difference (XSH) function.
Value range: 0 % to 20 %
Through selecting the module selection function one returns to controller parameter module
selection.
Page 2 displays additional parameters on a second page of settings.
The following settings apply to the 2-point-FUZZY controller:
ClO
-controller
2
parameters page 1
(2-point FUZZY)
The set point (W) function is used to specify the nominal value within the measuring range.
Measuring range
0..2 mg/l
The FUZZY controller is informed of the system characteristic through the specified delay time.
Value range: 0 sec to 60 sec
The set point difference (LW) function is used to specify the absolute interval between
switching point 2 and the set point.
Measuring range
0..2 mg/l
The switch difference (X2SD) function can be used to specify a switch hysteresis around
switching point 2. The stated percentage refers to the absolute value of switching point 2.
Value range: 0.0 % to 30.0 %
Through selecting the module selection function one returns to the controller parameter
module selection.
Page 2 displays additional parameters on a second page of settings.
417101816_Anhang09_ClO2.doc
Value range
0.00 mg/l to 2.00 mg/l
0 sec to 1200 sec (prelim time)
0 sec to 3600 sec (delay time)
Value range
0.00 mg/l to 2.00 mg/l
Value range
0.00 mg/l to 2.00 mg/l
ClO
Measuring Module
2
- 31 -
Rev.: 05-07/10