Télécharger Imprimer la page

Eaton PowerXL DH1 VFD Série Notice D'installation page 16

Publicité

Instruction Leaflet IL040029EN
Effective December 2017
North America cable and fuse sizes—440 Vac to 500 Vac ratings
Amp
Input current
Frame size
suffix
(VT/I
FR0
3D3
3.8
4D3
4.3
5D6
6
7D6
9.6
FR1
3D3
2.8
4D3
3.2
5D6
4.5
7D6
7.1
9D0
8.4
012
10.2
FR2
016
13
023
19.6
031
25.2
FR3
038
31.7
046
37
061
48.1
FR4
072
59.3
087
70.3
105
87.6
FR5
140
114.4
170
144
205
166.1
FR6
261
226.4
310
284.9
Notes
Line and motor cable size is selected according to UL 508C Table 40.3 for copper conductor rated 75 °C. Use only with copper wire rated 75 °C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4.
If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended.
FR0 is not available till June 2018.
EATON
16
www.eaton.com
NEC motor
Current
amp rating
(VT/I
)
L
)
at 460 V
at 40 °C
L
3
3
3.4
3.4
4.8
4.8
7.6
7.6
3
3
3.4
3.4
4.8
4.8
7.6
7.6
7.6
11
11
14
14
21
21
27
27
34
34
40
40
52
52
65
65
77
77
96
96
124
124
156
156
180
180
240
240
302
302
NEC
wire size (AWG)
Recommended
fuse
Line and
rating
motor
Ground
10
14
14
10
14
14
10
14
14
15
14
14
10
14
14
10
14
14
10
14
14
10
14
14
15
14
14
15
14
14
20
12
12
30
10
10
35
8
8
50
6
8
60
6
8
80
4
6
100
4
4
110
3
4
125
1
3
175
2/0
3
200
3/0
3
250
250 kcmil
3
400
2*2/0
3
400
2*4/0
3
PowerXL DH1 Series VFD
Terminal connection
size (AWG)
Line and
motor
Ground
26–10
18–10
26–10
18–10
26–10
18–10
26–10
18–10
26–10
18–10
26–10
18–10
26–10
18–10
26–10
18–10
26–10
18–10
26-10
18–10
20–6
12–6
20–6
12–6
20–6
12–6
6–2
14–4
6–2
14–4
6–2
14–4
6–1/0
10–1/0
6–1/0
10–1/0
6–1/0
10–1/0
1/0–350 kcmil
8–250 kcmil
1/0–350 kcmil
8–250 kcmil
1/0–350 kcmil
8–250 kcmil
2*(1/0–300 kcmil)
3–300 kcmil
2*(1/0–300 kcmil)
3–300 kcmil

Publicité

loading