ABB PVS800 Manuel D'exploitation page 21

Masquer les pouces Voir aussi pour PVS800:
Table des Matières

Publicité

17
No.
Name/Value
44.18
CUT-IN CHECK
ENA
OFF
ON
44.20 CUT-IN FREQ HIGH
50/60 Hz
44.19 CUT-IN FREQ LOW
44.21 CUT-IN VOLT LOW
44.19
CUT-IN FREQ LOW 100 = 1
45...65 Hz
44.20
CUT-IN FREQ HIGH 100 = 1
40...65 Hz
44.21
CUT-IN VOLT LOW
0...200%
44.22
CUT-IN VOLT HIGH 1 = 1%
0...200%
Update notice
FbEq
Description
Enables or disables the checking of cut-in conditions (start
conditions). Cut-in condition checking is based on measurements
from the NAMU board.
The limits for cut-in conditions are defined by parameters
CUT-IN FREQ LOW
below for more information.
Note: Check that the NAMU board is enabled (parameter
NAMU BOARD
0
Checking of cut-in conditions is disabled.
1
Checking of cut-in conditions is enabled.
02.18 GRID FREQUENCY
300 V
Defines the low limit for the frequency cut-in condition.
Hz
Low limit for the grid frequency
Defines the high limit for the frequency cut-in condition.
Hz
High limit for the grid frequency
1 = 1%
Defines the low limit for the voltage cut-in condition.
Low limit for the grid voltage
Defines the high limit for the voltage cut-in condition.
High limit for the grid voltage
...
44.22 CUT-IN VOLT
ENABLE) before enabling the cut-in conditions.
01.11 MAINS VOLTAGE
Region where PVS800 can be started
44.22 CUT-IN VOLT HIGH
Def.
OFF
44.19
HIGH. See the figure
40.02
47.5 Hz
50.05 Hz
95%
110%
T
B
R
R
R
R