Fault tracing

Alarm and fault messages generated by the inverter control
program
Message
HIGH UAC LEV (32A5)
9.01 FAULT WORD 1 b5
HIGH UAC PEAK(32A4)
9.01 FAULT WORD 1 b5
RT NET LOST (32A1)
9.11 SUPPLY FAULT WORD b9
LVRT RIDETRGH(32A0)
DCREF MIN RNG(32AB)
8.06 MPPT STATUS bit 8
DCREF MAX RNG(32AC)
8.06 MPPT STATUS bit 9
RUN DISABLE(FFAC)
8.06 MPPT STATUS bit 7
(bit=1 start enable)
AP PRG ERR (FFD6)
EXT DIO (7082)
AC UNDERFREQ (31A3)
Update notice
Cause
x
High AC voltage measured long
enough
x
High AC voltage peak
x
Supply voltage out of RT-area.
Missing phase(s) or frequency out
of the allowed range for 20 seconds
during synchronization.
x
AC voltage is lower than
U/Un LEVEL1
MPPT has reached the DC
x
reference minimum range.
x
MPPT has reached the DC
reference maximum range.
x
Cut-in conditions are not fulfilled.
x
Error in the adaptive program
x
Error in the RDIO module or module
configuration
x
NAMU grid monitoring has alarmed. Check group
What to do
Check parameters
VOLT LEV
and
TIME.
Check parameter
PEAK.
Check RT-area parameters
40.10...40.15.
Check network conditions.
Check that initialized base
frequency signal
correct.
40.10 RT
Alarm is cleared when the AC
voltage is greater than
Un LEVEL1
parameter settings in group
LVRT
CONTROL.
Check the settings of parameters
39.05 MPPT DC REF MIN
30.15 DCREF RANGE
Check the settings of parameters
39.04 MPPT DC REF MAX
30.15 DCREF RANGE
Check the settings of parameters
44.18...44.22.
Check the adaptive program for
errors. Check parameters
57.01...58.05.
Check that configuration for the
RDIO modules is correct in the
parameter group
MODULES. Replace the RDIO
module if the alarm is continuously
active.
MONITORING.
Check the grid condition.
40.21 TRP
40.22 TTRP VOLT
40.20 TRP VOLT
3.03
or
3.04
is
40.10 RT U/
+ 5%. Check the
40
and
ALARM.
and
ALARM.