5. Electrical connections

Connect the electrical conductors acc. to the instructions on
type label.
Make sure that all input cables are not live
(potential-free) when making the connec-
tions!
Impending danger by high power supply
voltage!
Take care of current transformers!
Also note that, ...
... the data required to carry out the prescribed
measurement must correspond to those
marked on the nameplate of the SINEAX I 552
(
measuring input,
and
power supply, see Fig. 6)!
... the resistance in the output circuit may not
overrange the current output value
15 V
max. [kΩ] ≤
R
ext
I
(I
= current output value)
AN
and not underrange the voltage output value
U
min. [kΩ] ≥
R
ext
2 mA
(U
= voltage output value)
AN
... the measurement output cables should be
twisted pairs and run as far as possible away
from heavy current cables!
In all other respects, observe all local regulations
when selecting the type of electrical cable and
installing them!
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 2. For measurement with
1st (lower) measuring range,
power supply connected to
terminals 8 and 9.
10
measuring output
[mA]
AN
[V]
AN
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 3. For measurement with
2nd (higher) measuring range,
power supply connected to
terminals 8 and 9.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 4. For measurement with
1st (lower) measuring range,
power supply connected to the
low tension terminal side
12 and 13.
I
= Measuring input
= Measuring output
= Power supply
Output
Output signal
10
11
12 13
+
4-20 mA
SINEAX I 552
Mat: 133752 /000000
0-1/5A / 50/60Hz
0
1A
5A
1
2
3
4 5
Input
Measuring range
Measured quantity
Fig. 6. Declaration to type label.
6. Adjustable measuring range by DC cali-
bration
DC calibration is performed at the user's
risk. The warranty is void if the calibration
seal is removed.
Reliably isolate the measuring input from
dangerous voltages.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 5. For measurement with
2nd (higher) measuring range,
power supply connected to the
low tension terminal side
12 and 13.
Calibration seal
0,5
Conformity
marks
85-230V AC/DC
40-400Hz 3VA
Works No.
(+)
+
6
7
8
9
Power
supply