Mitsubishi Electric CITY MULTI PUHY-HP-TNU-A Série Manuel D'installation page 43

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

(2) When MA remote controllers are connected
* Move the power jumper from
CN41 to CN40. *
1
* SW5-1: ON *
2
* Leave the power jumper
connected to CN41.
* SW5-1: ON *
2
*1 When a power supply unit is not connected to the centralized control transmission cable, move the power jumper from CN41 to CN40 on
only one of the outdoor units. Up to three system controllers can be connected to TB3 side.
*2 If a system controller is used, set SW5-1 on ALL of the outdoor units to ON.
*3 When a PAR-30MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
Maximum allowable length of control cables
Transmission cables via outdoor units
Transmission cables
Remote controller cables
*4 When extending the length of the transmission cables to 1000 m (3280 ft), consult your dealer.
(3) When a transmission booster unit is connected
TB7
TB7
Shielded cable
*1 Daisy-chain terminals (TB3) on outdoor units together in the same refrigerant system.
*2 Leave the power jumper connected to CN41.
Maximum allowable length of control cables
Transmission cables
Remote controller cables
Group 1
L
+ L
1
2
L
, L
1
3
m
+ m
1
TB7
L
+ L
1
2
L
+ L
6
5
1
2
* If the length exceeds 10 m (32 ft), the length that exceeds 10 m (32 ft) needs
to be included in the maximum allowable length of transmission cables
above.
Group 3
Group 5
+ L
+ L
, L
+ L
+ L
3
4
1
2
6
+ L
, L
, L
+ L
4
6
2
6
, m
+ m
+ m
+ m
2
1
2
3
4
Earth
+ L
+ L
+ L
, L
+ L
+ L
+ L
3
5
6
1
2
3
5
+ L
+ L
, L
+ L
+ L
+ L
3
4
4
3
5
7
Shielded cable
Sub remote controller
System controller
*4
+ L
, L
+ L
+ L
,
7
1
2
4