Mitsubishi Electric CITY MULTI PUHY-HP-TNU-A Série Manuel D'installation page 40

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

(2) YNU model
Outdoor unit model
PUHY-HP72YNU-A
PUHY-HP96YNU-A
PUHY-HP120YNU-A
PUHY-HP72YNU-A
PUHY-HP144YSNU-A
PUHY-HP72YNU-A
PUHY-HP96YNU-A
PUHY-HP192YSNU-A
PUHY-HP96YNU-A
PUHY-HP120YNU-A
PUHY-HP240YSNU-A
PUHY-HP120YNU-A
・The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one size
thicker in diameter. Make sure the power-supply voltage does not drop more than 10%. Make sure that the
voltage imbalance between the phases is 2% or less.
・Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord (design 60245 IEC57). For example, use wiring such as YZW.
・The user must ensure that this unit is connected only to a power supply system which fulfils the requirement
above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
Minimum cable size
Unit combination
Power
cable
5.3 (10)
5.3 (10)
8.4 (8)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
[mm
2
(AWG)]
Earth leakage circuit breaker
Ground
25 A 30 mA or
5.3 (10)
100 mA 0.1 sec. or less
30 A 30 mA or
5.3 (10)
100 mA 0.1 sec. or less
35 A 30 mA or
8.4 (8)
100 mA 0.1 sec. or less
25 A 30 mA or
5.3 (10)
100 mA 0.1 sec. or less
25 A 30 mA or
5.3 (10)
100 mA 0.1 sec. or less
30 A 30 mA or
5.3 (10)
100 mA 0.1 sec. or less
30 A 30 mA or
5.3 (10)
100 mA 0.1 sec. or less
35 A 30 mA or
8.4 (8)
100 mA 0.1 sec. or less
35 A 30 mA or
8.4 (8)
100 mA 0.1 sec. or less
MCA (A)
MOP (A)
(460 V)
(460 V)
17
25
20
30
21
35
17
25
17
25
20
30
20
30
21
35
21
35

Publicité

Table des Matières
loading

Table des Matières