Boiler Fixing; Probe-Electrode Positioning - Chappee TIGRA 2 CG510 Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.2 BOILER FIXING

To fit the burner to the boiler it is necessary to carry out the following:
Widen, if necessary, the insulating gasket holes (3, fig. 3).
Fix the flange (5) to the boiler door (1) using four screws (4) and (if necessary) the nuts (2) interposing
the insulating gasket (3) but keep unloosing one of the two upper screws (4) (see fig. 2).
Put on the flange (5) the burner combustion head, tighten the flange with the screws (6) and lock the
loose screw (4).
N.B.: The burner can be fixed with the variable dimension (A) (see fig. 4). Anyway, make sure that the
combustion head crosses completely the boiler door thickness.
Fig. 2
3.3

PROBE-ELECTRODE POSITIONING

ATTENTION
Ensure that the plate (3, fig. 5) is always
inserted in the flattening of the electrode.
Lean the probe insulator (4) against the cup (2).
TYPE
911T1
912T1
A
17
20016967
S7002
913T1
914T1
30
31
31
TYPE
A
911 T1
166
70
912 T1
180
170
913 T1
282
267
914 T1
317
302
3.5
±
0.3
3
6
GB
Fig. 3
D5012
A
Fig. 4
D5011
Fig. 5
2
A
±
0.3
1
4
D6088