ELMON inductive 74-312
Inductive signal transmission system
V10: If no error is present, then LED Power shows the function control (briefly off)
V31 and later: If no error is present, then LED Power shows the operating state (on)
V70 or later:
If an internal fault is determined during operation, the fault alarm will be saved The existing saved
fault alarms are emitted one after the other by the green LED (Power) via the number of pulses All
internally saved fault alarms are deleted after a switch-on process If there is a current internal fault,
then all red LEDs will be continuously lit If there is no current internal fault, the red LEDs display the
state of the connected safety contact strips Any internal faults during testing of signal input (fault
alarm 6) will become inactive if no more errors are discovered during testing
During the output of an error message, the number of output pulses indicates the error:
Pulse
Error message
1
Voltage supply outside of the valid value range
2
Inductive signal transmission system error
3
Output control Open faulty
4
Output control Close faulty
5
Data transmission with microcontroller faulty
6
Testing sensor input faulty (stationary safety contact edges) (Open/Close)

5.3 Connection terminals

STOP Opening terminals
STOP Closing terminals
STATIONARY Opening terminals
STATIONARY Closing terminals
Transmit 1, 2 terminals
24 V AC/DC terminals
L1 N terminals

6 Connecting the device

6.1 Prerequisites

• The signal cable must not be placed parallel to the motor cable or other power cables
• The supply voltage used for the ELMON inductive 74-312 must comply with the requirements for
safety low voltage (SELV)
• Cables installed outdoors or outside of the switching cabinet must be protected appropriately
• The protection class specified for this device is only ensured if the supply lines have been properly
clamped to the screw connections
relay output for controller - stop opening
relay output for controller - stop closing
safety contact edges - leading pillar opening
safety contact edges - leading pillar closing
stationary coil core
24 V AC/DC supply voltage
230 V supply voltage