Specific Safety And Work Instructionse - ELECTOR PUROFILL VA Manuel De L'utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PUROFILL-VA

1.6 Specific safety and work instructionse

The PUROFILL-VA tank system is only suitable for treating water for technical applications. The treated
water is not suitable for human nutrition.
Note that the treated or untreated aqueous solution can be aggressive. Observe the safety data sheets
for the filter material and wear protective clothing that complies with the regulations when working
with the filter system.
When starting up and if the water filter system has not been used for a long time, the filter should be
flushed with a quantity of water corresponding to twice the filter volume before use.
To avoid microbiological contamination, the filter should be rinsed once a year and the filter material
replaced.
Don't use microbiologically contaminated water or water of unknown quality as feed water for the
PUROFILL-VA water filter system without adequate disinfection.
The filter system must not be opened or dismantled during operation. The filter cartridge must not be
opened without first relieving pressure.
The stainless steel container is designed for a service life of 10 years. An exchange should take place
after this time.
Protect the container system from sunlight and mechanical damage. Do not use near heat sources
and open flames. Depending on the application, a safety valve must be installed in front of the input
connection in accordance with the European standard DIN EN 1717.
If the water pressure on the inlet side is higher than 10 bars, a pressure limiter must be installed in
front of the tank.
To avoid contamination from particles, a filter with filtration degree of <50 μm should be installed in
front of the tank.
All parts must be installed in accordance with the country-specific guidelines.
The container system must always be operated within the specified ambient temperatures.
Caution with frost: After commissioning, storage and transport of water-filled systems below 4 ° C
should be avoided. Frost can destroy the water filter system.