4. Electrical work
• 4-20mA / 1-5V / 0-10V / 0-10kΩ
1 Use 4-20mA / 1-5V / 0-10V
Connect the transmission cables to No. 11 and 12 on the terminal block (TB61).
No. 11 on the terminal block(TB61) : Plus side
No. 12 on the terminal block(TB61) : Minus side (Reference side)
2 Use variable resistor (0-10kΩ)
Connect the transmission cables to No. 9 and 10 on the terminal block (TB61).
Note:
The values of the "capacity setting" table on the previous page show the center
of the input value.
Cable length: Maximum 10m
• Remote switch Type A (4 bit - 8 setting)/Type B (1 bit - 1 setting)
Demand control is available by connecting remote switches with terminal No.10 - 14.
Make sure to use the non-voltage switch (for the remote switch)
Remote switch cable length : Maximum 10m
Remote switch : Minimum applicable load 12V DC, 1mA
Note:
When using intelligent multiple outdoor unit control function, input the capacity request
signal to the main interface which connects to the ref. address 0 outdoor unit.
• External function setting
This function is setting operation mode or stopping compressor, by the external signal.
TB62
Item
1-2 (IN1)
Forced Comp. OFF *1 Normal
3-4 (IN2)Item Fixed operation mode Cooling
*1 The operation continues during defrosting operation.
The "Forced Comp. OFF" signal should not be turned ON frequently. It should only
be used if an abnormality occurs.
Cable length : Maximum 10m
Remote switch : Minimum applicable load 12V DC, 1mA
Note:
When using IN1 with intelligent multiple outdoor unit control function, input
IN1 to the interface unit respectively. Input IN2 to the main interface which con-
nects to the ref. address 0 outdoor unit.
Caution:
The external input signals are separated by basic insulation from power sup-
ply for the unit.
The external input signals should be separated by supplementary insulation
from where user may touch in case that it is installed where user may touch.
Connect the terminals by using the ring terminals and also insulate the ca-
bles of adjoining terminals when wiring to terminal block.
4.1.5. Connecting External Output
Name Terminal block Item
OUT1 TB141 5-6
Operation Output
OUT2 TB141 3-4
Error Output
OUT3 TB141 1-2
Comp. ON Output
OUT4 TB142 5-6
Defrost Output
OUT5 TB142 3-4
Mode(Cool) Output
OUT6 TB142 1-2
Mode(Heat) Output
OUT7 TB143 5-6
Self protection Output OFF
OUT8 TB143 3-4
Pre-Defrost Output
*1 The output may not be available depending on connected outdoor unit models.
Cable length : Maximum 50m
Output specification : Non-voltage switch 1A, 240V AC/30V DC or less
10 mA, 5 V DC or more
*Connect the surge absorber according to the load at site.
Notes:
• External output signals are separated by basic insulation from other circuit
of interface.
• When intelligent multiple outdoor unit control function is selected, OUT2, OUT3,
OUT4, OUT7 and OUT8 will work individually on each interface.
Caution: When 2 or more external outputs are used, the power supply on
the output side should be the same.
OFF
ON
Remark
Forced Comp. OFF
Heating
Available when SW2-1 and SW2-2 are ON
OFF
ON
OFF
ON
Normal
Error
OFF(Comp. OFF) ON(Comp. ON)
OFF
ON(Defrosting)
OFF
ON(Cooling)
OFF
ON(Heating)
ON
*1
OFF
ON
TB61
TB62
4-20mA/1-5V/0-10V
Wired remote controller
(For maintenance)
TB143
TB142
<Photo 4.1.5>
X8
X7
X6
TB143
TB142
1
2 3 4 5 6
1
OUT8 OUT7
OUT6
<Photo 4.1.4>
At site
I/F
(
9
0-10 kΩ
10
11
+
(
12
13
(
14
TB61
1
IN1
2
3
IN2
4
TB62
TB141
X5
X4
X3
X2
TB141
2 3 4 5 6
1
2 3 4 5 6
OUT5 OUT4
OUT3
OUT2 OUT1
X1
9