ADDITIONAL CONTROLS

EMERGENCY FUNCTIONING
The two following failure cases are fore-
seen when the thermostat operates in
the described manner.
NO WATER PROBE
- Ventilation is always active
- The season change is made on the
basis of the difference between the set-
ting made and the actual ambient tem-
perature. If the ambient temperature
exceeds by a value equal to the dead
band, the Heating setpoint switches to
the Cooling mode. If the ambient tem-
perature drops by a value equal to the
VENTILATION CYCLES OF 2-PIPE SYSTEM WITHOUT AMBIENT PROBE
AMBIENT PROBE ABSENT (4 PIPES)
In this case the thermostat operates as
follows:
- OFF - Aux Mode
The valves are closed
The fan is off
- AUTO, V1, V2, V3 mode:
The operating season is decided
according to the position of the tem-
perature selector and it is activated by
the respective valve as shown in the
Figure
The ventilation in this case is always
performed according to the ON-OFF
cycles, however, increasing the ON
phase from the central position. In
this way the maximum ventilation can
be required with the selector at the
VENTILATION CYCLE OF THE 4-PIPE SYSTEM WITHOUT AMBIENT PROBE
dead band below the Cooling setpoint,
it switches to the Heating mode.
- The turning on/off of the resistance
does not depend in this case on the
temperature of the water but on the
sheer demand for the thermostat opera-
tion
AMBIENT PROBE ABSENT (2 PIPES)
In this case the thermostat operates as
follows:
- OFF - Aux Mode
The valve is closed
ON cycle
SetPoint
duration
Min value
Nil
20 C°
2'20"
'20"
Max value
Minimum value
Cold water valve opening, ventilation
period proportional to the deviation
of the median position
minimum position for cooling opera-
tion season and likewise there is maxi-
mum ventilation with the selector in
the maximum position. For the heating
operation season. The total duration of
the ON-OFF cycle is again 5'20''. The
ON cycle
Position
duration
'20"
Min value
20 C°
Nil
'20"
Max value
The fan is off
- AUTO, V1, V2, V3 mode:
The valve is always open.
Operating season always hot.
- The ventilation runs On-Off cycles.
The duration of the ON cycle is pro-
portional to the setpoint set in the
VMF-E4 panel. The total duration of
the ON-OFF cycle corresponds to
5'20''. The following table gives dura-
tion examples of various ON and OFF
cycles based on the position of the
temperature selector:
OFF cycle
duration
'20"
2'60"
Nil
SETPOINT
Hot water valve opening, ventilation
period proportional to the deviation
following table gives duration exam-
ples of various ON and OFF cycles
based on the position of the tempera-
ture selector:
OFF cycle
duration
Nil
'20"
Nil
AGLLI10/20NFJ 07/11_4528572_00
Keys used to
modify the
setpoint value
Maximum value
of the median position
37