4. Refrigerant Piping

Indoor unit connection example
Connect one R-Converter unit per indoor unit.
Connect the R-Converter unit to the liquid pipe.
The thermistor-L (liquid) is installed close to the connecting point of
the extension piping (liquid) for the indoor unit.
The thermistor-G (gas) is installed close to the connecting point of
the extension piping (gas) for the indoor unit.
Thermistor-G (gas)
Outdoor unit
MAX. 10 m
R-Converter unit
Piping connection size
Indoor unit capacity
Liquid pipe size (mm)
BTU
HP
07
09
1
ø6.35 × 0.8
12, 13
1.6
18
2
ø9.52 × 0.8
24, 30
2.5
∗R-Converter unit
ø6.35 × 0.8
If using a liquid pipe that is ø9.52 mm, use joint pipe "PAC-493PI" (op-
tional parts)or a locally procured tandem joint (ø6.35 →ø9.52 mm).
Additional refrigerant quantity
If necessary, add additional refrigerant to the unit by following the
calculation method given in the outdoor unit (PUMY) manual.
When calculating the refrigerant quantity, be sure to include the R-
Converter unit-to-indoor unit liquid pipe length.
Thermistor-L (liquid)
Indoor unit
Extension piping
connecting point (flare)
Refrigerant piping system
∗ For details, see PUMY series installation manual.
Install sections a, b, c, d and e as shown in the illustration to the R-
Converter unit.
A
A+B+C+D+a+b+c+d+e
L=A+B+C+D+e
r=B+C+D+e
H
30 m (Outdoor lower H
h
12 m
A
B
C
B
a
b
c
C
C
C
A
A+a+b+c+d+e
L=A+e
70 m, r=e
H
30 m (Outdoor lower H
A
h
12 m
B
a
b
c
C
C
C
C
The installation condition for the R-Converter unit - to - indoor unit
are as shown in the illustration below.
The refrigerant pipe length from the indoor unit to the R-Con-
verter unit must be less than 10 m and its height difference less
than 8 m.
Install the R-Converter unit within an indoor-unit-to-indoor-unit height
difference of 12 m.
Match the refrigerant piping size to the indoor unit.
Outdoor unit
R = MAX. 10 m
100 m
70 m
30 m
20 m)
L
R
D
d
e
C
C
A: Outdoor unit
B: First Branch
100 m
C: Indoor unit
30 m
D: Cap
20 m)
L
R
D
e
d
C
Indoor unit
R-Converter unit
R
Indoor unit
5