Single Phase Connections
The connections are marked on the terminal
block or on a label and are presented in the
table below.
SYMBOL
COLOR
GREEN/
YELLOW
N
WHITE
L
BLACK
DIMMING +
VIOLET
DIMMING -
GREY
DALI +
ORANGE
DALI -
ORANGE
Tx
GREEN
Rx
WHITE
3.3VDC +
RED
3.3VDC -
BLACK
0-10 VDC Dimming (If Applicable)
Dimming is controlled by means of a 0-10
VDC signal (to be provided by the installer) to
control the level of dimming. At 10 volts, the
output of the unit is 100%; at 0 volts, the output
will shut off. The DC dimming voltage should
not exceed 15 VDC. Increasing the voltage
from 10 VDC to 15 VDC will not result in
additional light output.
WARNING: Never connect the dimming wires
to the Hot or Neutral supply wires.
Variable Voltage Control
An analog 0-10 V active dimmer may be
connected to the two wires to control the
light output of the fixture. Multiple lights may
be connected to the same dimmer, as long
as the maximum current rating of the dimmer
is not exceeded.
The dimmer must be capable of sinking 0.5
mA per light.
Light output will vary
approximately linearly with control voltage,
with 10 V corresponding to 100% light output.
NOTE: Simply shorting the two wires together
will cause the light to shut off.
Page 4 of 24
Reliant™ EMEA/APAC High Bay
Taking into Operation
Prior to operating, check the luminaire for its
correct installation in compliance with these
operating instructions and other applicable
regulations.
CONNECTION
WARNING: Only fully certified equipment may
EARTH/
be put into operation.
GROUND
NEUTRAL
LIVE
Conditions for Use
DIMMING
The supply to the luminaire must include a
DIMMING
fuse which is capable of interrupting a 1.5 kA
DALI +
short circuit current.
DALI -
When used with steel wired armor or braided
TRANSMIT
cable the basket weave armor or braid is
FROM DRIVER
unable to carry the cable load without
RECEIVE
fracture. The cable must therefore be
FROM DRIVER
clamped and cleated to prevent pulling on
3.3V DC
the cable being transmitted to the cable
RETURN FOR
terminations.
3.3V
WARNING: Improper installation, operation,
or maintenance of this luminaire may result in
the invalidation of the warranty, certificate,
or declaration of conformity.
For maximum long term reliability and light
output, the luminaire must be installed in free
air.
Maintenance
This LED luminaire should require a minimum
amount of maintenance. If any unforeseen
repairs are required, please contact Dialight
or its authorized representative.
Inspection
Within
the
inspection routine the following should be
included:
 Protective hoses should be covering the
connection cables.
 Cable entries must be free of corrosion.
 The lens should be cleaned periodically as
needed to ensure continued photometric
performance. Clean the lens with a damp,
non-abrasive,
sufficient, use mild soap or a liquid cleaner.
 Inspect the luminaire to ensure that it is free
of any obstructions or contamination (i.e.
excessive dust build up). Clean with a non-
abrasive cloth if needed.
 Perform visual mechanical and electrical
inspections
recommend routine checks to be made
on a yearly basis. Frequency of use and
environment should determine this.
scope
of
maintenance
lint
free
cloth.
If
on
a
regular
basis.
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
Tel: +1 732 919 3119 Fax: +1 732 751 5778
It is recommended to follow an Electrical
Preventive
Maintenance
described in NFPA 70B: Recommended
Practice for Electrical Equipment.
Repairs / Overhaul / Modification
The equipment must be operated according
to the intended purpose in a perfect and
undamaged condition.
NOTE: Should the luminaire enclosure be
damaged, only a full luminaire replacement
will be permitted. In case of doubt, the
equipment should be returned to Dialight for
inspection/repair.
Disposal & Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal should be observed.
Secondary Retention
Part Number
HBXCAB48
48" Safety Cable
Connect safety cable to the retention
bracket on the luminaire (shown below).
When using a safety cable for secondary
retention, ensure minimum slack (no greater
than 0.3 m/1 foot) in cable after installation.
or
Retention Bracket
not
Cable type, size, material, and attachment
method to meet customer application and
to be appropriate with all local and regional
regulations.
We
Program
as
Description
9100127385599 REV A
www.dialight.com

Publicité

loading