C – SAFETY KIT
Capacitor banks are equipped as standard with a safety kit
 Each cubicle is equipped with its own smoke detector.
 If smoke is detected by the safety kit:
Beware, the capacitor bank can be under voltage even if the controller is switched off
The following operations must be undertaken to ensure the detector kit works
correctly:
Perform annual maintenance (cleaning, tightening) on the safety kit.
Conduct an annual check of the smoke detectors.
Change the smoke detector as often as recommended in the maintenance guide.
Any failure to follow procedures and warnings to the letter can lead to premature
failure, explosion, or an outbreak of fire in the equipment, and will automatically
invalidate the enclosure warranty.
(1)
Not included in 770 mm high enclosures without reactors, in version with circuit breaker with power ≤ 125 kVAr, in version
without circuit breaker with power ≤ 150 kVAr.
(2)
Legrand Cat. No. 041525.
(3)
For enclosures with forced ventilation.
(4)
Please contact your Legrand Group representative to request diagnostics on your affected capacitor bank enclosure.
_____________________________________________________________________________________________________
o "ALPTEC" controller power supply switched off.
o The contactors switch to the "open" position.
(2)
o Buzzer
on the front of the enclosure activated with transmission of an
audible and visual signal.
o An NC contact marked "X1/X2" opens to enable remote signalling.
This signalling must always be done by the customer.
(3)
o Fan
switched off.
 The fault is maintained until the capacitor bank
(1)
:
34
(4)
is switched off.