22 VIEWING ACTUATOR hISTORY

22.1 ACTIVITY

Select change in the MENU and turn to OK to confirm.
Select activity in the CHANGE menu and turn to OK to
confirm.
Select number of starts or running time to view total figures
since the actuator was manufactured. The system also includes
a separate counter which can be reset by the user.
Select total to view total number of starts.
To reset the partial counter, select reset partial and then
choose yes or no (this option is only displayed when the user is
in the change menu).
starts
/
12
hour:
this
data
relates
ber
of
times
the
actuator
has
the previous 12 hours and tells the user about recent service.
This is particularly useful when trying to establish whether the
actuator has been subjected to excessive use when performing modulating actions.
handwheel action: indicates whether the handwheel has been used since the last time a motorised
movement was made. (changes are only registered if they exceed 10% of travel).

22.2 ALARMS

Alarms are used to pinpoint the source of malfunctions. They are not permanent and are deactivated
when the fault is cleared. A blinking black square is shownon the screen to indicate that an alarm
has been activated. To read alarms: Select check in the MENU and turn to OK to confirm .
Select alarms in the menu CHECK menu and turn to OK to confirm.
Use the right-hand selector to scroll through any active alarms.
List Details
Details
locked motor open
Motor immobilised in open direction
locked motor close
Motor immobilised in close direction
jammed valve
Max torque reached during operation
torque sensor
Torque sensor fault
position sensor
Position sensor fault
direc of rot open
Opening direction of rotation anomaly
direc of rot close
Closing direction of rotation anomaly
overtravel
Position overshoot >5% after motor cut off
config. memory
Stored configuration data error
activity memory
Stored activity data fault
base memory
Base memory fault
excess starts
Start-up rate exceeds average for class of actuator.
See criteria for class in §23
This alarms never causes the actuator to stop operating.
lost phase
Phase missing on 3-phase supply
lost signal
4-20 mA signal lost (if positioner option active)
thermal overload
Motor thermal switch tripped
pumping
Actuator hunting action detected
24V auxiliary
Auxiliary power supply fault for external circuits (terminals 6-7)
battery low
If battery option used, the battery needs to be changed
no alarm
30
To check settings without making
changes, select check instead
of change in the menu.
ACTIVITY
return
number of starts
running time
starts last 12h
handwheel action
return
NUMBER OF
STARTS
to
the
num-
total
started
during
partial
reset partial

23 ACCESSING DATA ShEET

Select change in the MENU and turn to OK to confirm.
Select data sheet in the CHANGE menu and turn
to OK to confirm.
valve tag number
Select valve tag number to read or write valve ID.
Use the blue selector to change the first character and turn to
OK to confirm.
Change remaining characters using the same method.
Turn to OK when all of the characters have been entered and
continue until the menu is displayed again.
actuator number: this is the actuator's serial number. This information
is entered at the factory and is only shown in the CHECK menu.
entry code: for entering or changing a password, see below:
"Creating or changing passwords".
characteristics: parameter settings for correct operation of the
actuator (see details next page).
The following data is only shown in the CHECK menu.
operating class: indicates whether the actuator is designed for
on/off operation, class III control or class II control functions. This
item can be used to activate an alarm if the number of starts
is excessive (excess. starts alarm).
The number is the counted over the previous 12-hour period.
Limits are as follows:
On / Off:
360 starts in previous 12 hours
Class III:
1,200 starts in previous 12 hours
Class II:
21,600 starts in previous 12 hours
This alarms never causes the actuator to stop operating.
manufacture date: gives date product shipped from factory software version: installed software
release
Characteristics menu details
motor : this data indicates whether the motor has a 3-phase, single phase or DC
power supply (data from manufacturer)
protection: waterproof or explosion-proof version. The explosion-proof version prevents overriding
the thermal relay in the degraded mode/commands menu.
locked motor/s: Indicates the time the motor left energised when immobilised before power cut off.
Default: 10 seconds (manufacturer's data)
reverse delay/ms: Indicates time actuator halted following change in direction of rotation.
Default: 200 ms (manufacturer's data).
ratio position system: indication of gear stepdown ratio between output shaft and position sensor
for displaying stroke in number of revolutions (or in degrees for fractions of a revolution) (manufactu-
rer's data).
To check settings without making
changes, select check instead
of change in the menu.
DATA SHEET
return
valve tag number
actuator number
entry code
operating class
manufacture date
characteritics
software version
return
VALVE TAG NUMBER
MOV55VV
CHARACTERISTICS
return
motor
locked motor/s
reverse delay/ms
ratio position system
ext gear ratio 1/
thread mm
measured stroke
operating time
return
31