Technical Data - Victron energy Phoenix Inverter Compact 24/1200 Mode D'emploi

Masquer les pouces Voir aussi pour Phoenix Inverter Compact 24/1200:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

8. TECHNICAL DATA

Phoenix Inverter
INVERTER
Input voltage range (V DC)
Output
Cont. output power at 25 °C (VA) (3)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero load power in search mode (W)
GENERAL
Programmable relay (4)
Protection (2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60Hz and to 240V
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) Programmable relay which can be set for general alarm, DC undervoltage or genset start signal function
12 Volt
24 Volt
Operating temp. range: -20 to +50° C (fan assisted
cooling) Humidity (non condensing) : max 95%
Material & Colour: aluminium (blue RAL 5012)
EN55014-1, EN 55014-2, EN 61000-3-3
C 12/1200
C 24/1200
9,5 – 17 V
19 – 33 V
Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
1200
1000
900
2400
92 / 94
8 / 10
2 / 3
yes
a - g
Protection category: IP 21
Battery cables of 1.5 meter
G-ST18i connector
10
375x214x110
EN 60335-1, EN 60335-2-29
C 12/1600
C 24/1600
1600
1300
1200
3000
92 / 94
8 / 10
2 / 3
15

Publicité

Table des Matières
loading

Table des Matières