Automatic Defrost

At low room temperatures, frost may build up at the evaporator during
operation. The unit will automatically start defrosting and the POWER LED
blinking. The defrost control sequence is as follows:
A. When the unit operates in the cooling operation, drying operation, the
ambient temperature sensor senses the evaporator coil temperature is
below -1 °C, after the compressor will stop operating for 10 minutes or the
coil temperature up to 7 ℃, the unit restart to cool operating mode.
B. When the unit operates in the drying operation, once the coil
temperature sensor senses the temperature of the evaporator is below 40
℃ and the differential temperature between coil temperature and room
temperature is below 19 ℃ after the compressor operation for 20minutes,
the unit start defrosting for 5 minutes and the power indicator blinking.
5.4.5.

Overload Protection

In the event of a power loss, to protect the compressor there is a 3-minute
delay until the compressor restarting.
DRAINAGE
Self- evaporating system
The self-evaporating system uses the collected water to cool the
condenser coils for better efficient performance. There is no need to
empty the drainage tank in cooling operation except in drying operation
and high humidity conditions. The condensate water evaporates at the
condenser and is evacuated through the exhaust hose.
For continuous operation or unattended operating in drying operation,
please connect the attached drain hose to the unit. Condensate water
can automatically flow into a bucket or drain by gravity.