Textron GREENLEE DM-860 Manuel D'instructions page 23

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Specifications (cont'd)
Pollution Degree: 2
Battery: 9 V battery (NEDA 1604, JIS 006P or IEC 6F22)
Overload Protections:
µA and mA: (FS1) 1 A/600 V fast acting fuse, IR 100 kA, 13/32" x 1-1/2"
Amps: (FS2) 15 A/1 kV fast acting fuse, IR 10 kA, 13/32" x 1-1/2"
Volts, Ω, and Others: 1450 V peak, 1050 VAC RMS
Overvoltage Protection Categories: Meets the requirements for double insulation to IEC
61010-1 (1995), EN61010-1 (1995), UL3111-1 (6.1994), CSA C22.2 NO. 1010-1-92, and
IEC 61010-1 second edition draft (1999) to terminals:
ΩV
Terminal: Category III, 1000 VAC and 1000 VDC;
Category IV, 600 VAC and 600 VDC
A Terminal: Category III, 1000 VAC and 1000 VDC; Category IV, 600 VAC and 600 VDC
µA and mA Terminal: Category III and Category IV, 600 VAC and 300 VDC
Overvoltage Installation Categories
These definitions were derived from the international safety standard for insulation
coordination as it applies to measurement, control, and laboratory equipment. These
overvoltage categories are explained in more detail by the International Electrotechnical
Commission; refer to either of their publications: IEC 1010-1 or IEC 60664.
Overvoltage Category I
Signal level. Electronic and telecommunication equipment, or parts thereof. Some examples
include transient-protected electronic circuits inside photocopiers and modems.
Overvoltage Category II
Local level. Appliances, portable equipment, and the circuits they are plugged into. Some
examples include light fixtures, televisions, and long branch circuits.
Overvoltage Category III
Distribution level. Permanently installed machines and the circuits they are hard-wired to.
Some examples include conveyor systems and the main circuit breaker panels of a building's
electrical system.
Overvoltage Category IV
Primary supply level. Overhead lines and other cable systems. Some examples include cables,
meters, transformers, and other exterior equipment owned by the power utility.