Test Operation - Panasonic U-8ME3XPQ Manuel D'installation

Masquer les pouces Voir aussi pour U-8ME3XPQ:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 44
Confirmation of the set mode
The following items can be confirmed by setting mode 1 (H1P
led is off)
Check the led indication in the field marked
1
Indication of the present operation state
-
normal
-
abnormal
-
under preparation or under test operation
H1P
H1P
H2P
H2P
2
Indication of COOL/HEAT selection setting
1
When set to COOL/HEAT change-over by each individual
outdoor unit circuit (= factory setting).
2
Indication on master unit when COOL/HEAT change-over is
carried out by outdoor system connected in multiple system-
combination.
3
Indication on slave unit when COOL/HEAT change-over is
carried out by outdoor system connected in multiple system-
combination.
(*)
H1P
H1P
H2P
H2P
(*)
(*)
1
2
3
(*) This setting = factory setting.
3
Indication of low noise operation state
-
standard operation (= factory setting)
-
operation
L.N.O.P
H1P
H1P
H2P
H2P
4
Indication of power consumption limitation setting
-
standard operation (= factory setting)
-
operation
DEMAND
H1P
H1P
H2P
H2P
U-8~16ME3XPQ
Urban Multi air conditioner
4PW16786-1C
.
H3P
H3P
H4P
H4P
H5P
H5P
H6P
H6P
H7P
H7P
H3P
H3P
H4P
H4P
H5P
H5P
H6P
H6P
H7P
H7P
L.N.O.P
H3P
H3P
H4P
H4P
H5P
H5P
H6P
H6P
H7P
H7P
DEMAND
H3P
H3P
H4P
H4P
H5P
H5P
H6P
H6P
H7P
H7P

8.4. Test operation

NOTE
In case of 18~48 type: check the setting and the
indication results. Refer to chapter "Caution for
18~48 type units" on page 19.
After turning on the power supply, the unit cannot
be started until the H2P initialisation led goes off
(maximum 12 minutes).
Check the stop valves
In case of 5~16 type: Make sure to open the suction and
discharge gas line stop valves and the liquid line stop valve.
In case of 18~48 type: Make sure to open the oil pressure
equalizing stop valves as well.
After installation, perform the test operation.
Unless the test operation is performed, the error code "U3" is
shown on the remote controller and the unit cannot be operated.
Performing the test operation
1
To protect the compressor, make sure to turn on the power
supply 6 hours before starting operation.
2
Set to setting mode 1 (H1P led is off) (refer to "Setting mode 1"
on page 17).
3
Press the
button for 5 seconds (or longer when the
BS4 TEST
unit is at a standstill). The test operation starts when the H2P led
blinks and the remote controller indicates
and
(external control).
It may take 10 minutes to bring the state of refrigerant uniform
before the compressor starts, but that is not a malfunction.
The test operation is automatically carried out in cooling mode
during 15~30 minutes.
Depending on the situation, the refrigerant running sound or the
sound of a magnetic solenoid valve may rise during this
operation.
The following items are automatically checked:
-
Check for miswiring
-
Check if stop valves are open
-
Check of refrigerant charge
-
Automatic judgement of piping length
NOTE
When you want to terminate the test operation,
press the
BS3 RETURN
running for 30 seconds and then stops. During
test operation it is impossible to stop the unit with
the remote controller.
4
After the test operation (maximum 30 minutes), the unit
automatically stops. Check the operation results by the outdoor
unit led indication.
H1P
H1P
H2P
H2P
normal
abnormal
Indoor units cannot be checked individually. After the
test operation is finished, check the indoor units
individually via the remote controller.
The led indication changes during this operation, but
that is not abnormal.
Please attach the front plate of the oudoor unit in
order to prevent incorrect judgement during operation.
(test operation)
button. The unit will keep
H3P
H3P
H4P
H4P
H5P
H5P
H6P
H6P
H7P
H7P
Installation manual
18