5. Faults
Call the service agents immediately if faults in the
battery or the charging unit are found. Recorded
data as described in item 3. must be made avail-
able to the service agent. It is recommended that
a service contract is taken out with our agent.
6. Storage and taking out of operation
Refreshening charge shall be carried out latest if
the open circuit voltage is decreased to the fol-
lowing guide values:
– Gel: 2.075 Vpc respectively 4.15 V (4V-block),
6.225 V (6V-block), 8.3 V (8 V-block), 10.375 V
(10V-block), 12.45 V (12V-block)
– AGM: 2.095 Vpc respectively 6.285 V
(6V-block), 12.57 V (12V-block).
To store or decommission cells/blocks for a
longer period of time they should be fully charged
and stored in a dry frost-free room.
To avoid damage the following charging
methods can be chosen:
1. Annual refreshing charge acc. to item 2.4.
Gel-batteries A400, PowerCycle, A500, A600
and A700 can be stored without refreshing
charge for maximum 24 months at ≤ 20 °C. At
average ambient temperatures of more than
the nominal temperature shorter intervals can
be necessary.
2. Float charging as detailed in 2.3.
9.1 AGM-Types
9.1.1. Marathon L/XL
Discharge time t
10 min
n
Capacity C
[Ah]
C
1
/
1.60Vpc C
n
6
L12V15
6.50
L12V24
10.6
L12V32
14.1
L6V110
48.4
L2V220
87.4
L2V270
106
L2V320
135
L2V375
155
L2V425
169
L2V470
186
L2V520
204
L2V575
220
L2V575plus
231
XL12V50
20.0
XL12V70
28.6
XL12V85
34.6
XL6V180
74.3
U
[V] (2 V cell)
1.60
f
U
[V] (6 V block)
4.80
f
U
[V] (12 V block)
9.60
f
All technical data refer to 20 °C.
9.1.2 Marathon M-FT
Type
Nominal
voltage
[V]
M6V200FT
M12V35FT
12
M12V50FT
12
M12V60FT
12
M12V90FT
12
M12V100FT
12
M12V105FT
12
M12V125FT
12
M12V155FT
12
M12V190FT
12
All technical data refer to 20 °C.
en
12

7. Transport

Cells and blocks must be transported in an
upright position. Batteries without any visible
damage are not defined as dangerous goods
under the regulations for transport of dangerous
goods by road (ADR) or by railway (RID). They
must be protected against short circuits, slip-
ping, upsetting or damaging. Cells/blocks may
be suitable stacked and secured on pallets (ADR
and RID, special provision 598). It is prohibited
to staple pallets.
No dangerous traces of acid shall be found on
the exteriors of the packing unit.
Cells/blocks whose containers leak or are dam-
aged must be packed and transported as class
8 dangerous goods under UN no. 2794.
In case of air transport, batteries which are part
of any equipment must be disconnected at their
terminals, and the terminals must be protected
against short-circuits. This is in order to avoid
the risk of any incidents like fire etc.
8. Central degassing
The ventilation of battery rooms and cabinets,
respectively, must be carried out acc. to
EN 50272-2/IEC 62485-2 always. Battery rooms
are to be considered as safe from explosions,
when by natural or technical ventilation the con-
centration of hydrogen is kept below 4% in air.
30 min
1 h
1
/
1.60Vpc C
1.60Vpc C
2
1
8.50
9.90
13.9
15.8
18.7
21.4
65.0
75.5
127
150
155
183
190
225
221
262
247
291
277
324
304
357
334
394
350
412
28.2
32.7
39.1
45.6
48.1
57.5
100
120
1.60
1.60
4.80
4.80
9.60
9.60
C
[Ah]
10
1.80 V
per cell
6
200
35
47
59
86
100
100
121
155
190
3 h
5 h
10 h
1.70Vpc C
1.75Vpc C
1.80Vpc
3
5
10
13.2
13.0
14.0
21.0
21.5
23.0
27.9
30.0
32.0
102
107
112
186
198
220
229
243
270
271
288
320
318
337
375
360
382
425
399
428
470
438
474
520
486
520
575
508
547
601
42.3
45.5
50.4
57.0
61.5
66.6
73.5
80.5
85.7
147
165
179
1.70
1.75
1.80
5.10
5.25
5.40
10.2
10.5
10.8
Constant current discharge [A].
U
= 1.75 V per cell
f
1 h
3 h
5 h
135
55.1
36.2
26.4
10.1
6.55
34.2
13.5
8.82
40.1
16.5
10.9
64.0
24.9
15.9
70.0
29.0
18.9
70.0
28.5
18.7
88.1
37.1
23.3
103
43.5
29.0
130
54.5
35.5
This standard contains also notes and calcula-
tions regarding safety distance of battery open-
ings (valves) to potential sources of sparks.
Central degassing is a possibility for the equip-
ment manufacturer to draw off gas. Its purpose
is to reduce the safety distance to potential
sources of ignition.
Only block batteries equipped by a tube junction
for central degassing must be used for this
application.
The installation of the central degassing must be
carried out in acc. with the equivalent installation
instructions. During each battery service also the
central degassing must be checked (tightness of
tubes, laying in the direction of the electrical
circuit, drawing off the end of the tube to the
outside).
9. Technical Data
The following tables contain values of either
capacities (C
) or discharge rates (constant cur-
n
rent or constant power) at different discharge
times (t
) and to different final voltages (U
n
All technical data refer to either 20 °C or 25 °C
(depends on battery type).
Length
Width
Height
max.
max.
max.
[mm]
[mm]
[mm]
181
76
167
168
127
174
198
168
175
272
166
190
209
136
265
209
136
265
209
202
265
209
202
265
209
202
265
209
270
265
209
270
265
209
270
265
209
270
265
220
172
235
262
172
239
309
172
239
309
172
241
1) Includes installed connector
Length
Width
Height
max.
max.
max.
[mm]
[mm]
[mm]
361
132
250
280
107
189
280
107
231
280
107
263
395
105
270
395
105
287
511
110
238
559
124
283
559
124
283
559
125
318
).
f
1)
Weight
approx.
[kg]
6.50
10.0
13.5
21.3
16.0
18.3
24.2
26.5
28.8
32.6
35.0
37.3
38.9
19.1
23.6
28.3
29.0
Weight
approx.
[kg]
34.0
14.0
18.0
23.0
31.0
33.0
35.8
47.6
52.8
62.0

Publicité

Table des Matières
loading

Table des Matières