Installing The Equipment - Groupe Atlantic CORFIRST Série Notice D'installation, D'utilisation Et D'entretien

Réservoirs d'eau à serpentins de 500 à 3000 litres
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 6
A data plate listing all the information about the tank is located on the foot of the tank in line
with the thermometer and on the casing. Please take note of these details before contacting
After-Sales Service.

3. INSTALLING THE EQUIPMENT

• Two lifting rings on the top of the tank enable it to be lifted into place. Do not use the
tappings to lift the tank, as this will damage the interior coating.
• Place the tank and its safety unit (and/or safety valve) in a frost-free place.
• Position it as near as possible to the most-used taps.
• If it is placed outside occupied areas, insulate the pipework. If the device needs
to be installed in a location where the ambient temperature is always above 35°C,
ensure the space is ventilated.
• Ensure that the supporting structure is strong enough to take the weight of the tank
when it is filled with water.
• Allow a minimum of 1 metre in front of the flange (or manhole) for regular maintenance
of the tank. Sufficient space should also be left above the tank for inspecting the
magnesium anode – see the anode instructions.
• Fit a retention tank with a drain beneath the tank if it is located in a loft or above premises
in use.
• The safety unit and/or safety valve must be accessible.
• A drain connection must be provided equipped with a funnel.
• The lower tapping allows the tank to be drained fully.
• The tank only operates in the vertical position.
10.02.2020
CORFIRST / CORSUN 2 / CORFLOW
EN
Page 17 / 82

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières