Safety Valve; Hydraulic Connection Diagram; Electric Elements - Groupe Atlantic CORFIRST Série Notice D'installation, D'utilisation Et D'entretien

Réservoirs d'eau à serpentins de 500 à 3000 litres
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 6
5.3.2. Safety valves:
The safety valves are fitted to the tank inlet using a T (see diagram below).
1 single G 1¨ unit
EN
No non-return valve or flap should ever be fitted between the safety valve or safety unit
and the tank.
A non-return flap preceded by a valve must be fitted to the cold water inlet if the tank is
equipped with a safety valve. To avoid scaling of these components, operate the safety unit
at least once a month by moving its controls to various positions.

5.4. Hydraulic connection diagram

See Appendix A page 63.

6. ELECTRIC ELEMENTS

Tank heating time with resistor(s):
These estimated heating times are given for storage at 60°C and cold water at 10°C.
On CORFIRST and CORFLOW Shielded option
It is possible to add 5 to 30 kW shielded resistors, according to the following recommended
combinations.
CORFIRST
Page 20 / 82
SAFETY UNIT
On cold water inlet only
1¼¨ kit with 2 G 1¨ units
500
Heated volume
248
5 kW
3:00
10 kW
1:30
15 kW
-
25 kW
-
Heated volume
199
30 kW
0:25
CORFIRST / CORSUN 2 / CORFLOW
tank connector diameter
Safety valve/non-return flap/valve
750
900
1000
378
441
463
4:30
5:15
5:15
2:15
2:30
2:30
1:30
1:45
1:45
0:45
1:00
1:00
301
364
385
0:35
0:45
0:45

SAFETY VALVE

On tank inlet
Valve diameter ≥
1500
2000
630
755
7:15
8:45
3:45
4:30
2:30
3:00
1:30
1:45
506
562
1:00
1:05
U0594061-D