Whirlpool 3LCGD9100 Instructions D'installation page 8

Masquer les pouces Voir aussi pour 3LCGD9100:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Plan installation to use the fewest number of elbows and turns.
A
Allow as much room as possible when using elbows or making
turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the center of the bottom dryer back.
The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer.
Vent System Length
Maximum length of vent system depends upon the type of vent
used, number of elbows, and type of exhaust hood.
Maximum Vent Length
102 mm (4") Exhaust Hoods
Box
Rigid Metal Vent
No. of 90° turns
Box Hood and Louvered Style
0
39.6 m (130 ft.)
1
38.1 m (125 ft.)
2
35.1 m (115 ft.)
3
32.3 m (106 ft.)
4
98 m (98 ft.)
If dryer is installed in a confined area, such as a bedroom,
bathroom, or closet, provision must be made for enough air
for combustion and ventilation. (Check governing codes and
ordinances.) See "Recessed Area and Closet Installation
Instructions" in the "Location requirements" section.
A 102 mm (4") outlet hood is preferred. However, a 64 mm
(2
1
") outlet exhaust hood may be used. A 64 mm (2
2
outlet creates greater back pressure than other hood types.
For permanent installation, a stationary vent system is required.
Multiple Dryer Venting
I A main vent can be used for venting a group of dryers. Main
vent should be sized to remove 5663 l/min (200 CFM) of air
per dryer. Large-capacity lint screens of proper design may be
used in the main vent if checked and cleaned frequently. The
room where the dryers are located should have make-up air
equal to or greater than the airflow of all the dryers in the
room.
I A back-draft damper kit is needed and is available from a
laundry distributor; it should be installed in the vent of each
dryer to keep exhausted air from returning into the dryers
and to keep the exhaust in balance within the main vent.
Unobstructed return air openings are required.
8
B
Exhaust Air Flow
A. Good
B. Better
Louvered
64 mm (2
1
Angled Hood Style
39.3 m (129 ft.)
36.3 m (119 ft.)
33.2 m (109 ft.)
30.5 m (100 ft.)
28 m (92 ft.)
1
")
2
Each vent should enter the main vent at an angle pointing in the
direction of the airflow. Vents entering from the opposite side
should be staggered to reduce the exhausted air from interfering
with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning fluid fumes. Fumes create
acids which, when drawn through the dryer heating units, can
damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic
cleaning of the vent system.
If an exhaust hood cannot be used:
") Angled
2
C
A. Exhaust hood or elbow
B. Wall
C. Main collector vent
D. Horizontal vent
E. 180° sweep elbow
F. Vertical vent
G. Roof
The outside end of the main vent should have a sweep elbow
directed downward. If the main vent travels vertically through the
roof, rather than through the wall, install a 180° sweep elbow on
the end of the vent at least 610 mm (2 ft.) above the highest part
of the building. The opening in wall or roof shall have a diameter
13 mm (
1
") larger than the vent diameter. The vent should be
2
centered in the opening.
Do not install screening or cap over the end of the vent.
A
30˚ max.
B
air ow
A. Individual dryer vent
B. Main vent
B
A
D
Min. 300 mm (12") clearance
above any accumulation
12" min.
(305 mm)
of snow, ice, or debris such
as leaves.
610 mm (24")
min. above
24" min.
(610 mm)
F
highest point
of building
E
G
C

Publicité

Table des Matières
loading

Table des Matières