Determine fan powers:
1. Enter the flow rates from the design calculation for the three ventilation profiles "At home", "Away" and "Boost" in the
unit characteristic curve for supply and extract air (cf. Fig. 36).
ⓘ We recommend entering the following values in the ventilation profiles:
• Reduced ventilation ≙ Ventilation profile "Away"
• Nominal ventilation ≙ Ventilation profile "At home"
• Intensive ventilation ≙ Ventilation profile "Boost"
Total air flow rates by fan-assisted ventilation according to DIN 1946-6:2019-12
Ventilation for mo-
Ventilation type
isture protection
Fan flow rate [m
/h]
3
59
D p
f a
Pa
è
à
ú
ó
é
á
û
ô
ê
â
2. The approximate fan powers to be set (in %) can be read from the ventilation profiles at the points of intersection of
the flow rates and the system characteristic curve (cf. Fig. 36). Enter these in the corresponding ventilation profile via
the easyControls software or the control element KWL-BE Touch (cf. Fig. 37).
Example: Ventilation profile "Away" = 31 %
Ventilation profile "At home" = 55 %
Ventilation profile "Boost" = 78 %
3. Select the ventilation profile "At home" under the menu item "Homepage".
4. Select the menu item "Configuration".
Reduced
ventilation
138
Fig. 36
10 %
â
20 %
ê
30 %
ô
40 %
û
50 %
á
60 %
é
70 %
ó
80 %
ú
90 %
à
100 %
è
V · m
/h
3
22
Nominal
Intensive
ventilation
ventilation
197
256
EN
Fig. 37