E-1: TERMINAL LABEL
A low voltage remote control wiring interface is provided on the unit.
The connections for the low voltage remote wiring are located on
two terminals adjacent to the exhaust fan outlet (or adjacent to the
supply fan outlet on the 7000 unit). All field installed wiring must be
low voltage class II.
R
W
C
EMOTE
ALL
ONTROL
Optional wall control requires a 4 wire LVT-24 gauge (or
equivalent). This remote wall control runs on 12 VDC.
L
V
C
OW
OLTAGE
ONTROLS
All other terminals are dry contacts.
Low Voltage terminal control consists of the following:
W
C
ALL
ONTROL
4 wire LVT 24 gauge minimum
O
(N
CCUPIED
IGHT SET BACK
24 VAC, needs dry contact
LOW - COM - HIGH
Remote fan switching requires a single pole, double throw switch
(SPDT)
F
I
R
O
AN
NTERLOCK
ELAY
UTPUT
Dry contact closes on ventilation or defrost. Used to control
external fan.
Black
Red
OCCUPIED
TIMER/
SENSOR
F
F
CLASS 2 VOLTAGE
NOTE:
Connections are all dry
contacts except wall control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
VE0002A
TERMINAL CONTROL DIAGRAMS
) T
/S
IMER
ENSOR
(FF)
WALL CONTROL
Green
Yellow
LOW
COMMON
HIGH
Appendix E
E-2: WALL CONTROL CONNECTION
Two types of remote wall controls are available:
1. Slide Switch Wall Control with fan switch and dehumidistat
control (for 6LC and 12LC units)
2. Pool Plus Wall Control with fan mode selection, dehumidistat
control and high speed recirculation mode (for 7000 unit).
The remote wall controls work with the microprocessor electronic
control within the unit to control ventilation sequences. Each wall
control has different features and require 4-wire connection to the
unit as shown below.
Without the wall control, fans can be operated with a remote fan
switch as shown in Appendix E-4.
NOTE:
When using a wall control, never use the the LOW, COMMON and
HIGH terminals.
VE0006A
18
WALL CONTROL
Black
Green
Red
Yellow
LOW
OCCUPIED
TIMER/
SENSOR
COMMON
HIGH
F
F
CLASS 2 VOLTAGE
NOTE:
Connections are all dry
contacts except wall
control
and 24VAC power supply.
Use of 24VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
Wall
Control