free SPDT (single pole, double throw) contacts, max. switch rating
250 V – 1 A, DC power output 24 V.
Sensor P:
Terminals for wiring connections to pressure or float switch respec-
tively for On/Off pump control.
TLS:
Terminals for wiring to low water cut-out or overflow alarm respec-
tively. The differing possibilities of dry-run protection and their res-
pective wiring are depicted in Fig. 3.
WSK:
Terminals for wiring to motor integrated overload protection devices
WSK (thermal winding contacts) or PTC-sensors. Hook switches
and potentiometers located on the unit board must be set for the
different unit functions. These are described in Chart 1.

6 Commissioning

All functional adjustments on the ER1(-A) control unit as laid out in
Chart II must have been set prior to initially starting-up of the connec-
ted pump plant.
Chart 1: Functions of hook switches and potentiometer
Switch/Pot.
Functions
S 2
Effect reversal for sensor input:
S 2 open: Pump runs on closed sensor contacts
S 2 closed: Pump runs on open sensor contacts
S 3
Test run:
S 3 open: Test run activated
S 3 closed: Test run deactivated
S 4
Effect reversal for TLS input:
S 4 open: Pump stops on low water (pressure boosting)
S 4 closed: Pump starts on overflow (submersible pump)
S 5
Switch is not active with standard design
S 6
Effect reversal for the TLS input
S 6 top closed:
S 6 bottom closed: Pump starts on overflow
S 7
Switch for function extension Output option
P 1
Setting to suit motor full load current
P 2
Time delay after pump stop command (0 - 2 min)
P 3
Time delay for stop on low water / start on overflow
Chart 2: Settings of hook switches and potentiometers for different applications
Switch/Pot.
S 2
S 3
S 4
S 6
6P1 (R 10)
6P2 (R 27)
6P3 (R 48)
→ Hook switch open, 1 → Hook switch closed
** 0
** Factory settings
Technical modifications reserved!
Pump stops on low water
Pressure boosting
*0*
0
0
top
2
0.5

7 Maintenance

The control unit is maintenance-free.
8 Faults - Causes and Remedies
Blinking green light:
Motor overload cut-out has responded.
No automatic reset after rectification of fault cause.
To reset: Switch selector switch to "0"
Red light On:
Switch-off due to low-water or overflow respectively.
Automatic reset after rectification of fault cause.
Reset is also possible by switching the selector switch to "0".
SSM:
On each fault event and overflow alarm.
If the fault cannot be remedied please contact your Installer or
your nearest WILO service.
(Fig. 2)
Fire services
*1*
0
0
top
see motor name plate
2
0.5
Waste disposal**
0
1
1
bottom
0
0
7