Lenze 9400 E94ASHE Série Instructions De Montage page 68

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

8
Wiring the device modules
Communication modules
DIP switch
Pos.
Description
Addressing of the bus node
O
N
d
c
b
a
Baud
Fig.16-3
On memory modules with front-panel DIP switches you can set
the node address (labelling "1" ... "64") and
ƒ
the baud rate (labelling "a" ... "d").
ƒ
Note!
If all address switches are in the "OFF" position when the standard device is
switched on, the configurations stored under codes C00350 (node address)
and C00351 (baud rate) are valid.
Switch off the voltage supply of the standard device and then switch it on
again to activated changed settings.
Setting of the node address
The node address of the drive results from the sum of all address switches in ON position.
Setting of the baud rate
d
c
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
Displays
Pos.
Colour
MS
Green
DE
Red
BS
Green
BE
Red
68
64
32
16
8
4
2
1
CAN Address
Arrangement and labelling of the DIP switches
b
a
Baud rate
ON
OFF
10 kbps
OFF
ON
20 kbps
ON
ON
50 kbps
ON
OFF
125 kbps
OFF
ON
250 kbps
OFF
OFF
500 kbps
ON
OFF
800 kbps
OFF
OFF
1000 kbps
ON
ON
Autobaud
Condition
On
On
Signalling according
to DR303-3
Description
Communication module is supplied with voltage.
Communication module is not accepted by the standard device
(see notes given in the documentation for the standard device).
CANopen state ("Z")
CANopen error ("F")
9400CAN003
EDK94ASH24 DE/EN/FR/ES/IT 3.1

Publicité

Table des Matières
loading

Table des Matières