AERMEC VMF-E1X Manuel D'utilisation Et D'installation page 22

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Power supply
Max input power (excluding loads controlled by TRIACs)
Digital inputs
Analogue inputs
Digital outputs
Assembly
Protection rating
Storage conditions
Operating conditions
Software class
Voltage
Max. current
Power supply
Accessory control outputs (Valves-Plasmacluster germicidal
lamp, etc.)
EC digital input
MS digital input - Sliding contact
SP digital input
Analogue inputs (SA-SW)
Analogue input (SC)
TTL local serial
RS485 supervision serial
Output power supply
22
AVMFE1LJ 1704 - 6795741_00
E1 TECHNICAL FEATURES
230V AC +/-10%, 50-60 Hz
4.5VA
3 free contacts
No. 3 for reading NTC 10K probes
No. 5 - 230V AC with Triac
On the machine
IP20 (referring to the containment plastic)
-20T80°C, humidity 80% non-condensing
0T50°C, humidity 80% non-condensing
Class A
OUTPUTS: Control of fan
230V AC
0.7 A
E1 CONNECTION SPECIFICATIONS
Screw terminals, 5mm pitch
Cable section - min=0.5mm
Screw terminals, 5mm pitch
Cable section - min=0.5mm
Maximum cable length = 30m
Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
Maximum cable length = 100m
Maximum cable length = 3m
Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
Maximum cable length = 30m
Quick plug-in connections
Maximum cable length = 3m
Quick plug-in connection
Maximum cable length = 30m
Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
Maximum cable length = 30m
Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
Maximum cable length = 500m
12V dc screw terminals, 3.81mm pitch
Cable section - min=0.2mm
Maximum cable length = 30m
max=2.0mm
2
2
max=1.3mm
2
2
max=1.0mm
2
2
max=1.0mm
2
2
max=1.0mm
2
2
2
max=1.0mm
2
2
max=1.0mm
2

Publicité

Table des Matières
loading

Table des Matières