Minimum Framing Dimensions - Napoleon Altitude Ax36Nte-2 Manuel D'installation

Table des Matières
Les langues disponibles

Les langues disponibles

rough framing
EN
3.4

minimum framing dimensions

SIDE WALL
C
Horizontal vent sections: A minimum clearance of 3" (76mm) on the top of the vent to combustibles and 2"
(51mm) on the sides and bottom of the vent to combustibles is required.
Vertical vent sections: A minimum clearance of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required.
Ref.
B
C
D
E
22
W415-10007507 / --0 / 08.05.25
12"
(305mm)
B
Do not put objects in front of the appliance
(minimum distance of 4 feet)
AX36-2
35 3/4" (908mm)
42 15/16" (1091mm)
60 5/8" (1540mm)
E
AX42-2
42 3/4" (1086mm)
19" (483mm)
48" (1219mm)
67 11/16" (1719mm)
D